Specifications
Overview: ATS with Power Distribution
14 Automatic Transfer Switch with Power Distribution
ATS panel board, right side
Input conductors from the utility mains connect
to the Source 1 input switch. See the
InfraStruXure Power Generation System
Installation Manual for connection
instructions. WARNING: Only a certified
electrician should connect power to the ATS!
Behind this access panel are the volt-sensing
circuit boards. Use a Phillips or standard
screwdriver to remove the panel.
The Source 1 current transformers monitor
the input current from each phase of the input
from the utility mains. The data gathered from
these current transformers is displayed on the
Total Load by Phase screen, accessed through
the Load Meter menu on the display interface.
Behind this access panel is the Source 2 volt-
sensing (S2 PT) circuit board. Use a Phillips or
standard screwdriver to remove the panel.
The Source 2 control transformer outputs
120VAC and 18VAC to the Source 2 motorized
switch. The transformer steps down 480V or
208V input.
Control power from Source 2 is supplied
through the Source 2 fuse block to the Source 2
transformer and powers the Source 2 motorized
switch.