Datasheet
Model AR4038 & AR4038I
>Physical capacity: 38 Rack spaces
>Integrated APC PDU: 11 outlets NEMA
12 outlets IEC
>Max thermal load recommended: 3.6kW
>Noise reduction: 18.5dB
>Power consumption: 101 watts
>Weight: 200kg / 439 lbs
>Equipment weight max: 250kgs / 550 lbs
>Dimensions HxWxD: 1950x750x1130mm
77 x 30 x 44 in
Standard Features
Floor space requirements:
Enclosures are designed to be placed with their back
directly against a wall. Clearance of 200mm / 8” on
both sides of the cabinet is essential for normal
operation.
Ventilation system:
Each ultra-low-noise exhaust fan module has a
1.2 kW maximum recommended total thermal load
(or 4,100 BTU / hr). The 38U CX has 3 of these. The
24U Cabinet has 2 and the 18U Cabinet has 1.
Noise reduction:
18.5 dB broadband noise reduction, measured 1.0 m
/ 39” in front of the enclosure (
HP and Dell servers
A soundproofed ‘Server Room in a Box’ which
allows for IT deployment wherever and whenever it
is needed, saving space, cost and deployment time.
NetShelter
®
CX Enclosure
Model AR4024 & AR4024I
>Physical capacity: 24 Rack spaces
>Integrated APC PDU: 12 outlets NEMA
13 outlets IEC
>Max thermal load recommended: 2.4kW
>Noise reduction: 18.5dB
>Power consumption: 68 watts
>Weight: 170kgs / 373 lbs
>Equipment weight max: 280kgs / 615 lbs
>Dimensions HxWxD: 1285x750x1130mm
50.6 x 30 x 44 in
Model AR4018 & AR4018I
>Physical capacity: 18 Rack spaces
>Integrated APC PDU: 13 outlets NEMA
14 outlets IEC
>Max thermal load recommended: 1.2kW
>Noise reduction: 18.5dB
>Power consumption: 39 watts
>Weight: 138kgs / 304 lbs
>Equipment weight max: 310kgs / 680 lbs
>Dimensions HxWxD: 1015x750x1130mm
40.4 x 30 x 44 in
/ 39” in front of the enclosure (
HP and Dell servers
were used as noise source in noise reduction
measurements)
Mobility:
4 x heavy duty castor-type wheels
Front wheels have 360°rotation for manoeuvrability
and rear wheels have fixed front-to-back motion for
stability
Rear and side access:
Detachable rear side panels, left and right, for
equipment installation and maintenance access
Detachable rear fan modules gives completely open
rear rack access
Cable management:
75 mm / 3” width full-height vertical 0U accessory
channels located on each side at the front, middle,
and rear of the rack
Grounding:
All equipment installed within a NetShelter CX
should have conventional grounding via power
cables, but unlike conventional metal-case cabinets,
the NetShelter CX has no requirement for additional
grounding in the form of ground strapping or pipe
earthing etc. The enclosure shell is constructed
entirely from non-conductive materials and the rack
is completely isolated from outside contact.
Door locking:
Key operated lock
Warranty:
2 year warranty