Datasheet
Product Description and Inventory: Vertical Mounting Rails
20 NetShelter VX Enclosure: Unpacking, Installation, Customization
How to re-position the vertical rails using the horizontal braces
You can re-position the two front, the two rear, or all four of the vertical rails along the horizontal
braces to accommodate your equipment. You can re-position the vertical rails whether they are
configured for 19 inch or 23 inch equipment. The illustration shows re-positioning the two front
vertical rails but the procedure is the same for all of the vertical rails.
1. Remove the side panels from the enclosure.
2. Use the 5-mm hex wrench (included) to remove the hex-head screws in the slots of the vertical
rails.
3. Locate the new position for the vertical rails.
4. Insert a caged nut into the appropriate holes at the new position on the upper and lower
horizontal braces.
5. Place the mounting rail at the new position.
Insert a hex-head screw through the rail into
the caged nuts in the upper and lower
horizontal braces. Tighten the screws to
secure the vertical mounting rail to the
horizontal braces.
6. Repeat steps 2-5 for the opposite side of the
enclosure.
Warning
When the vertical rails are mounted to the side braces, no more than 1000 lb
(453.6 kg) of equipment should be mounted in the enclosure.
See “How to Remove and Install the Side Panels” on page 10.
Note
You may have to adjust the position of the horizontal braces up or down to align
with the vertical rails.
See “How to move a brace” on page 23.
See “How to install and remove caged nuts” on page 24.