Enable foreign
device registration
Select the check box to register the NMC with a BACnet broadcast
management device (BBMD).
NOTE: You need to register your NMC as a foreign device with a BBMD if there
is no BBMD currently on the subnet of the NMC, or if the NMC uses a different
local port to the BBMD.
In the above example:
• BBMD A manages the broadcast messages to NMCs V and W.
• BBMD B manages the broadcast messages to NMCs X and Y.
• Only NMC Z needs to register with a BBMD A or B as a foreign device, as
there is no BBMD present on its subnet.
• Once registered, NMC Z can receive broadcast messages from the BBMD
with which it is registered, and can send messages to the BBMD, which
broadcasts them to all devices on its subnet, and to the other BBMDs on the
network via the IP router.
Status
The status of the foreign device registration (FDR):
• Foreign device registration inactive
FDR will be inactive if:
– FDR is enabled and BACnet is disabled
– FDR is disabled and BACnet is enabled
– FDR is disabled and BACnet is disabled
• Registration successful
FDR has completed successfully.
• Registration rejected
FDR has not completed successfully. The NMC will retry registration
automatically, but you can also toggle the Enable foreign device
registration check box to prompt the NMC to retry registration.
• Registration sent
The FDR request has been sent, but it has not yet completed.
BACnet/IP
Broadcast
Management Device
The IP address or fully qualified domain name (FQDN) of the BACnet broadcast
management device with which this NMC card will be registered.
Port The port of the BBMD with which this NMC card will be registered.
Option Description
Subnet 1 Subnet 2 Subnet 3
BBMD A BBMD B
NMC V
Port: 47808
NMC W
Port: 47808
NMC Y
Port: 47809
NMC X
Port: 47809
NMC Z
Port: 48100
IP Router