UPS Network Management Card 3 User Guide59
BACnet/IP
Device Name
A name for this BACnet device, which must be unique on the BACnet network.
The default device name is “BACn”+ the last eight digits of the NMC MAC
address. The minimum length is 1, the maximum length is 150 characters, and
special characters are permitted.
Network Protocol
Select the protocol to be used:
• BACnet/IP
APDU Timeout
The number of milliseconds the NMC will wait for a response to a BACnet
request. Acceptable range: 1000-30000. The default value is 6000.
APDU Retries
The number of BACnet requests attempts that the NMC will make before
aborting the request. Acceptable range: 1–10. The default value is 3.
Device
Communication
Control Password
The Device Communication Control service is used by a BACnet client to instruct
a remote device (e.g. a BACnet-enabled NMC) to stop initiating, or stop
responding to all APDUs (except the Device Communication Control service) for
a specified duration of time. This service can be used for diagnostic purposes.
Specify the Device Communication Control password to ensure that a BACnet
client cannot control the BACnet communication of an NMC without first
providing the password set here. The password is required to be between 8 and
20 characters, and must contain:
• A number.
• An uppercase character.
• A lowercase character.
• A special character.
It is recommended to update the password when you first enable BACnet. You
do not need to know the current password to update the password.
Option Description
Local Port
The UDP/IP port the NMC uses to send and receive BACnet/IP messages.
Acceptable range: 5000–65535. Default: 47808.
NOTE: The address of a BACnet/IP-enabled NMC is defined as the IP address
of the NMC and the local port.