For more information on PowerChute shutdown sequences, see “Sample Shutdown Scenarios” in
the PowerChute Network Shutdown User Guide on the APC website.
During the comparison of the PowerChute Required Shutdown time and the NMC Maximum
Required Delay/Outlet Group Power Off Delay, the largest value is used. For example, if the
PowerChute client command line shutdown duration is set to 8 minutes, but the UPS Low Battery
Duration is 10 minutes, the NMC will use the larger value of 10 minutes for the Maximum Required
Delay.
In Forced Negotiation, the NMC polls the PowerChute Clients to get their required shutdown time.
As a result it can take up to ten minutes for the Maximum Required Delay/Outlet Group Power Off
delay values to update.
PowerChute never changes the NMC Low Battery Duration field value.
With PowerChute Network Shutdown v3.x or higher, the Maximum Required Delay value is never
used by the NMC for a UPS with outlet groups.
UPS General screen
Path: Configuration > UPS
This screen is not available for all UPS devices.
Some of the options explained below might NOT display for some UPS devices.
Field Description
UPS Name A name to identify the UPS.
UPS Position The physical orientation of the UPS, rack or tower.
Audible Alarm
Enable or disable the audible alarm of the UPS, and, for some UPS
devices, define the condition that will cause the alarm to sound.
LCD Language
Preference
Specify which language you want to use for your UPS display.
LCD Display
Disable or enable write-access to the UPS display interface.
When disabled, the user still has read-access to most screens, but not to
sub-screens on the Control and Configuration menus.
Battery Health Alarm
Warning Time
Sets the number of days before the critical battery replacement alarm is
displayed on the UPS LCD. Set to -1 to display no notification warning.
Battery Health Alarm
Sleep Time
Sets the number of days that the UPS LCD battery alarm should sleep
before it is displayed, after it is first acknowledged. Set to -1 to display no
further warnings once the warning is first acknowledged.
Last Battery
Replacement
Enter the month and year of the most recent UPS battery replacement.
Number of Batteries
or
External Batteries
The number of batteries, excluding built-in batteries, that the UPS has.
Some devices that have more than 16 batteries must add batteries in
quantities of 16 (e.g., 16, 32, 48, etc.), but can then be adjusted to the
correct value.