For more information about the delays and settings, see “Shutdown on Configuration menu”,
“Universal I/O screens”, and “Outlet Groups on Control menu”.
Actions on the UPS screen for devices WITH Outlet Groups
For more information about the delays and settings, see “Shutdown on Configuration menu”, and
“Outlet Groups on Control menu”.
Action Description
Reboot UPS
Outlet Groups
Applies a Shutdown Immediately, AC Restart command to all outlet groups (see
“Outlet Groups on Control menu”). Click Next to see specific details on timing and
delays.
Turns off the output power of the Switched Outlet Groups and then, if present, the
Main Outlet Group. Any outlet group to which the action is applied waits the number of
seconds configured for its “Reboot Duration” and “Power On Delay”. (Then, the outlet
groups turn on if AC utility power is available, or waits to turn on until AC utility power
is available. See “What are Outlet Groups?”).
The UPS turns on if AC utility power is available, or waits to turn on until AC utility
power is available.
Turn On UPS
Outlet Groups
Turns on the Main Outlet Group, if present, and then all Switched Outlet Groups. This
option displays only if the UPS is currently turned off. Click Next to see specific details
timing and delays.
The UPS and outlet groups then turn on.
Turn Off UPS
Outlet Groups
Turns off the output power of the Switched Outlet Groups and then, if present, the
Main Outlet Group. Any outlet group to which the action is applied remains off until
you turn on its power again. Click Next to see specific details on timing and delays
Put UPS Outlet
Groups to Sleep
Puts the UPS outlet groups into sleep mode by turning off the output power of the
UPS for a period of time defined by the following parameters. Click Next to see
specific details on timing and delays
The outlet groups wait the times configured as their “Power Off Delay” before
turning off their power.
When input power returns, the UPS turns on output power after two configured
periods of time elapse: “Sleep Time” and “Power On Delay”.
The UPS then turns off. After the hours configured as “Sleep Time” elapse, the UPS
turns on if AC utility power is available, or waits to turn on until AC utility power is
available.
Put UPS in
Bypass
Return UPS from
Bypass
These options control the use of bypass mode, which allows maintenance to be
performed at the UPS without turning off power at the UPS.
This option is only available for certain Smart-UPS models.