User Manual
18UPS Network Management Card 3 User Guide
Universal I/O on Status menu
Path: Status > Universal I/O
This option is not available for all UPS devices.
Temperature & Humidity displays the name, alarm status, temperature, and humidity (if supported) for each
sensor. Click the name of a sensor to edit the name and location and to configure its thresholds and its
hysteresis. See “Temperature and Humidity screen” for more details.
Input Contacts displays the name, alarm status, and state (open or closed) of each contact. These are
automatically found and displayed here when you install the environmental accessory. Click the name of an
input contact for detailed status or to configure its values. If contacts are configured and disabled, they do not
display here. See “Input Contacts screen” for more details.
Output Relay displays the name and state (open or closed) of each relay. These are automatically found and
displayed here when you install the environmental accessory. Click the name of an input contact for detailed
status or to configure its values. See “Output Relay screen” for more details.
Recent Environmental Events displays events that are related to your environmental monitoring, for example
a temperature threshold violation or a warning message about an environmental monitor input contact. Click
the More Events link to see a full list of recent events.
Pack Status
Errors for the battery pack only, not including the individual cartridge errors. Errors
are logged as events and can be:
• temperature not in range
• general errors
• communication errors
• a disconnected pack frame
• firmware is incompatible with the hardware
Battery Cartridge 1 and (if present) Battery Cartridge 2
Health
This can be OK, battery near end of life, battery lifetime exceeded, or measured
battery near end of life for the cartridge.
Errors are logged as events.
Installation Date The date when individual cartridges were installed. You can edit this date.
Predicted
Replacement Date
The UPS calculates when the battery should be replaced.
The Health field above is derived from this date.
Status
This is specific to the cartridge. See “Pack Status” above for general pack errors.
Errors are logged as events and can be:
• disconnected cartridge
• cartridge needs replacement
• cartridge temperature is too high: critical
• cartridge temperature is too high: warning. This usually but not always displays
before critical above.
Field Description