User`s guide

25UPS Network Management Card 2 User’s Guide
2. With outlet groups, the Power Off Delay for the outlet group supplying power to the PCNS client.
*The
PCNS SHUTDOWN REQUIRED TIME = the shutdown delay + the shutdown command duration.
When the default of 70 seconds is added, the time is always rounded up to nearest minute. E.g., a
total here of 3 min 50 sec is rounded up to 4 min; a total of 2 min is still rounded up to 3 min.
Notes:
The 70 sec. mentioned is the default OS shutdown time for PCNS.
PCNS never changes the NMC Low Battery Duration field value.
With PCNS v3.x, the Maximum Required Delay value is never used by the NMC for a UPS with
outlet groups.
UPS General screen
Path: Configuration > UPS General
This screen is not available for all UPS devices.
Some of the options explained below might NOT display for some UPS devices.
Field Description
UPS Name A name to identify the UPS.
UPS Position The physical orientation of the UPS, rack or tower.
Audible Alarm
Enable or disable the audible alarm of the UPS, and, for some UPS devices,
define the condition that will cause the alarm to sound.
LCD Language
Preference
Specify which language you want to use for your UPS display.
Display
Disable or enable write-access to the UPS display interface.
When disabled, the user still has read-access to most screens, but not to sub-
screens on the Control and Configuration menus.
Last Battery
Replacement
Enter the month and year of the most recent UPS battery replacement.
Number of Batteries
or
External Batteries
The number of batteries, excluding built-in batteries, that the UPS has. Some
devices that have more than 16 batteries must add batteries in quantities of 16
(e.g., 16, 32, 48, etc.), but can then be adjusted to the correct value.
External Battery Cabinet The battery cabinet Amp-Hour rating of an external battery source.
Force Negotiation: UPS WITH outlet groups
IF THEN
PCNS
Req. Shutdown
Time
NMC
Low Battery Duration
Power Off Delay
for the PCNS outlet
group is increased
to equal
PCNS
Req. Shutdown
Time
sec