User`s guide

19UPS Network Management Card 2 User’s Guide
Network on Control menu
Path: Control > Network > Reset/Reboot
Use these options to reset various Network Management Card options and the UI.
Action Description
Reboot
Management
Interface
Restarts the management interface (e.g. the Web user interface, the CLI) by logging you off.
The UPS and NMC devices are not rebooted.
Reset All
1
Caution:This resets all configured values in the management interface you are using, e.g. the
Web user interface.
Clear the Exclude TCP/IP check box to reset ALL configuration values to their defaults.
Select the Exclude TCP/IP check box to reset all values except how this device obtains its
TCP/IP configuration values (default is DHCP).
Reset Only
1
TCP/IP: Reset how this device obtains its TCP/IP configuration values to the default DHCP.
Event Configuration: Reset all changes to event configuration, by event and by group, to
their default settings. See “Notification menu”
UPS to Defaults: Reset only UPS settings, not network settings, to their defaults.
This option is only available when you have an environmental monitor connected.
Lost Environmental Communication Alarms: Clear any environmental alarms that are
caused by lost communication with an external sensor. For example, if a temperature sensor
is disconnected and causes an alarm, resetting lost environmental alarms returns the alarm
status for that sensor to Normal.
Note: To clear alarms for a sensor that is connected to the universal sensor port of an
AP9631 NMC, reconnect the sensor or restart the NMC.
Control Policy: Reset the settings that define how the NMC will respond to alarms that are
detected at the Dry Contact I/O Accessory.
1
Resetting may take up to a minute. The UPS name you configured will not be reset (see “UPS General
screen”).