18UPS Network Management Card 2 User’s Guide
When the state of the outlet group is on:
Off Immediately
Off with Delay: Turn off the group after the number of seconds configured as Power Off Delay
(see “Shutdown on Configuration menu”).
Reboot Immediately: Turn off the group immediately, then turn it on after the number of seconds
configured as Reboot Duration (see “Shutdown on Configuration menu”) and Power On Delay.
Reboot with Delay: Turn the outlet group off after the number of seconds configured as Power
Off Delay, then turn it on after the number of seconds configured as Reboot Duration and Power
On Delay.
For some UPS devices, when the state of the outlet group is on and the UPS is on battery:
Shutdown Immediately, AC Restart: Turn off the group immediately. After the number of
seconds configured as Reboot Duration and Power On Delay, check that AC utility power has
returned and the UPS can support the minimum return runtime demand, then turn on the group.
Shutdown with Delay, AC Restart: Turn off the group after the number of seconds configured
as Power Off Delay. After the number of seconds configured as Reboot Duration and Power
On Delay, check that AC utility power has returned and the UPS can support the minimum return
runtime demand, then turn on the group.
After you select an action, click Next to view a detailed description of the action, including the duration of any
delays. Click Apply to commence the action.
Security on Control menu
Path: Control > Security > Session Management
The screens gives details about users who are logged on, the interface they are using (e.g. the Web user
interface, the CLI), their IP address, and how long they have been logged on.
If you have sufficient rights, click on the name to see what means of authentication were used to validate the
user. You can then also use the Terminate Session button to log off a user.