User`s guide

UPS Network Management Card 2 User’s Guide990-4879
web
Access: Super User, Administrator
Description: Enable access to the user interface using HTTP or HTTPS.
For additional security, you can change the port setting for HTTP and HTTPS to any unused port from 5000 –
32768. Users must then use a colon (:) in the address field of the browser to specify the port number. For
example, for a port number of 5000 and an IP address of 152.214.12.114:
http://152.214.12.114:5000
Example: To prevent all access to the user interface for HTTPS, type:
web -s disable
xferINI
Access: Super User, Administrator. This command only works through serial CLI.
Description: Use XMODEM to upload an .ini file while you are accessing the command line interface
through a serial connection. After the upload completes:
If there are any system or network changes, the command line interface restarts, and you must log on
again.
If you selected a baud rate for the file transfer that is not the same as the default baud rate for the
NMC,
you must reset the baud rate to the default to re-establish communication with the
NMC.
xferStatus
Access: Super User, Administrator
Description: View the result of the last file transfer.
See the Users Guide for descriptions of the transfer result codes.
Option Argument Definition
-h enable | disable Enable or disable access to the user interface for HTTP.
-s enable | disable
Enable or disable access to the user interface for HTTPS.
When HTTPS is enabled, data is encrypted during transmission and
authenticated by digital certificate.
-ph <http port #>
Specify the TCP/IP port used by HTTP to communicate with the NMC (80
by default). The other available range is 5000–32768.
-ps <https port #>
Specify the TCP/IP port used by HTTPS to communicate with the NMC (443
by default). The other available range is 5000–32768.