Installation Manual
How to Install Multiple Management Cards
Overview
When installing more than one management card, such as the Network Management
Card 2 (NMC 2), the Out of Band Management Card, etc., you must install the cards
in the order described in this document. This is because they share a serial link with
the UPS. Installing the cards in any other order might result in operational failure.
Before you start
The following table identifies the priority of the cards you will be installing.
Management cards that have more control over the UPS have higher priority.
• Level 6: Exerts total control
• Level 5: Exerts wide, but not total, control
• Level 4: Exerts limited control
• Level 3: Passes commands to the UPS
• Level 2: Exerts no control
• Level 1: Exerts no control and must be installed closest to the UPS
Management Card Priority
Network Management Card 2 (AP9630, AP9631, AP9635)
1
Network Management Card 1 (AP9617, AP9618, AP9619)
2
Level 6
Out of Band Management Card (AP9608)
3
Level 5
Relay I/O Module (AP9613, AP9610) Level 4
Interface Expander Card (AP9607
4
, AP9624) Level 3
Building Management Integration Card (AP9622)
5
Level 2
Environmental Monitoring Card Level 1
1. Attach no more than two Network Management Cards to a UPS.
2. Network Management Cards AP9617, AP9618, and AP9619 are discontinued and
replaced by AP9630, AP9635 and AP9631, respectively.
3. The AP9608 is discontinued and replaced by AP9635.
4. The AP9607 is discontinued and replaced by AP9624.
5. Attach only one Building Management Integration Card to a UPS.The AP9622 card is
discontinued and replaced by AP9635.