Specifications
Tower Units Rack-mount Units
Long battery life
By packaging the batteries in an enclosure
separate from the UPS electronics, the
batteries operate at reduced temperatures.
Battery life is further enhanced through
CellGuard intelligent battery management
with high precision FastCharge™ and au-
tomatic true-load battery tests.
APC Smart-UPS XL increases your
availability with N+1 batteries
Extended battery packs running in parallel
with internal batteries provide both extend-
ed runtime, and also redundancy if a
battery should fail. Smart-UPS XL battery
packs are hot-swappable so you never have
to take down your mission-critical loads to
service the unit. Novell approves this
product for network protection, without
additional external conditioners.
Fault tolerance
Redundant batteries increase Smart-UPS XLs
fault tolerance. This feature eliminates unit
shutdown due to a single battery’s failure.
Simple maintenance
A battery change usually requires trained
service personnel or an expensive electri-
cian. However, this is not the case with APC’s
Smart-UPS XL and RMXL. The modular
Smart-UPS XL lets the user easily replace
battery packs in minutes while the protected
equipment remains up and running.
UXBP24 and UXBP48 Battery packs
The UXBP24 and UXBP48 are Ultra-
extended run Battery Packs designed to
be used with Smart-UPS products. The
combination provides expandable and
extended-run power protection for maxi-
mum up-time at an economical price.
They are ideal for mission critical applica-
tions where ultra-long runtimes are
essential. The UXBP24 and UXBP48 are
24V and 48V offerings, respectively.
UXBP24 and UXBP48 offer:
• Low installation & servicing costs-
Polarized connectors ensure a safe and
fast installation or replacement, eliminat-
ing the need for an electrician and
expensive service contracts.
• Space efficient- Battery packs are
designed to be stacked 4 high.
• Flexible- Battery packs can be used with
either the Smart-UPS XL or Smart-UPS
RMXL products.
Smart-UPS XL, RMXL and UX Battery Packs
15
For more information about all APC products, go to www.apcc.com
SPECIFICATION SU700XLNET SU1000XLNET SU2200XLNET SU1400RMXLNET SU2200RMXLNET SU3000RMNET
Ships with PowerChute plus software Support for Windows NT/2000, Novell NetWare, Windows 95/98, SCO UnixWare, SCO OpenServer, and Linux.
Includes agent plug-ins for Compaq Insight Manager, HP Top Tools, and IBM NetFinity Manager (NT and NetWare platforms.)
Input Line - 6 ft. line cord NEMA 5-15P NEMA L5-30P NEMA 5-20P NEMA L5-30P NEMA L5-30P
Output Receptacles 6 NEMA 5-15R 8 NEMA 5-15R
Number of SmartSlot bays 1 Smart Slot Bay included
Maximum Dimensions (H x W x D) (in) 8.5 x 6.7 x 17.3 17 x 7.7 x 21.5 8.8 x 19 x 17.8
Net Weight (lb) 53 60 121 115 124 129
Shipping Weight (lb) 58 65 140 134 143 145
Replacement Battery Cartridge RBC 7 RBC 7 RBC 11 RBC 11 RBC 11 RBC11
“T” Level for Service Options T3 T3 T4 T4 T4 T4
OPERATION SU700XLNET SU1000XLNET SU2200XLNET SU1400RMXLNET SU2200RMXLNET SU3000RMNET
Nominal Input Voltage 120 Vac, single phase, 50 or 60 Hz (auto-selectable)
Transfer Time (typical) 2 milliseconds, includes detection time
On-Battery Output Voltage Pure sine wave output at 120 Vac +/-5%, -10% after low battery warning, synchronized to utility line
SmartBoost and SmartTrim Operation On-line operation for input between 90 to 145 Vac. Output will be 103 to 132 Vac. SmartBoost increases voltage
12% if input is 90 to 103 Vac. SmartTrim reduces voltage 12% if input is 145 to 132 Vac. Transfer points are user
adjustable using software.
Capacity (Volt-Amps, Watts) 700, 450 1000, 670 2200, 1600 1400, 950 2200, 1600 3000, 2250
Surge energy rating,
320 Joules, 6.5kA 480 Joules, 6.5kA
peak current capability
Normal, common mode clamping 0 ns, <5ns typical, meets UL 1449
response time
Normal mode surge voltage let <0.3% of peak typical
through (IEEE 587 Cat. A 6kV test)
Batteries Sealed, maintenance-free lead acid batteries with a 3-6 year typical lifetime. 3 hour typical recharge time to 90%.
Ambient Operation 10,000 ft. (3,000 meters) max. elevation, 0-95% humidity non-condensing; 32 to 104 deg.F (0-40 deg. C)
Storage Conditions 50,000 ft. (15,000) meters max.elevation; 5 to 113 deg. F (-15 to 45 deg. C)
Audible noise at 1 meter <42 dBA <42 dBA <53 dBA <45 dBA <53 dBA
from surface of unit
BTUs/hr. 100 120 305 155 155 375
BATTERY PACK OPTIONS SU700XLNET SU1000XLNET SU2200XLNET SU1400RMXLNET SU2200RMXLNET SU3000RMNET
Extended runtime SU24XLBP SU24XLBP SU48XLBP SU48RMXLBP SU48RMXLBP SU48BP
Ultra-extended runtime UXBP24 UXBP24 UXBP48 UXBP48 UXBP48 N/A