Datasheet

Dry Contact I/O SmartSlot Card
5
Item Name Description
Universal I/O
ports 1 and 2
These support the AP9335T/ TH and AP9810 dry
contact accessories
USB cable
connector
Connecting this to your PC enables usage of the
Configuration Utility.
Reset button Use an appropriately sized, non-metallic tool to
press the Reset button. There are two options:
• Press and hold button [LED turns off], release in
less than 20 seconds [Card reboots with
NO reset].
• Press and hold button [LED turns off], continue
holding for 20 seconds [LED turns red, card resets
to factory settings and reboots].
Status indicator SOLID GREEN indicates communications and
operations are fine.
FLASHING GREEN indicates the Card is initializing.
FLASHING RED indicates a communication fault.
SOLID RED indicates a non-operational fault with
the UPS, not the Card: see KBase, # FA174931.
Dip switches These are located near the back of the front panel on
the right-hand side.
See “Configuring the Dip Switches” .
Output relay
terminals
Connections for alarm outputs.
See “Itemizing the input contact and output relay
terminal blocks” and “Ratings for input contacts and
output relays” .
Input contact
terminals
Connections for control inputs.
See “Itemizing the input contact and output relay
terminal blocks” and “Ratings for input contacts and
output relays” .
Cord grip Supports the cabling that is used to control external
devices, or to connect up external switches. The
bare wires connect to the terminal blocks on the
Card.
The cord grip is plastic and can secure a single cord
with a diameter range of 5.8 – 10mm. This limits the
number of conductors (inside the cord) and the
power ratings.