User Manual
considers an attempt to communicate with a
remote device has failed.
Post Alert Data Settings option
Use this option's configuration display to identify the IP or address you want the NetBotz
Appliances monitored by your StruxureWare Central server to send their alert data.
When a NetBotz Appliance is discovered by StruxureWare Central, the hostname of the
StruxureWare Central is added to the NetBotz Appliance. This enabled the StruxureWare
Central to receive alert postings from the NetBotz Appliance. If your server does not use
DNS, you will need to change the alert post entry on the NetBotz Appliance to the IP Address
of the StruxureWare Central server.
Note: This display also can be accessed when using Network Settings, a Server
Administration Settings option in the System menu, to change the Public (LAN1)
tab's Hostname or IP Address settings: when asked if you want to update the NetBotz
Appliance post settings, click Yes.
Element Description
Current StruxureWare Central Hostname The Hostname defined in the Network
Settings option's Public (LAN1) tab.
Current StruxureWare Central IP Address The IP Address defined in the Network
Settings option's Public (LAN1) tab.
Select the Address to Use for Sending Alert
Data
Select an IP address or hostname from the drop-
down list, or type in the hostname or IP address
you want the monitored NetBotz Appliances to
use to post alert data.
Note: If any of the NetBotz Appliances you want
the StruxureWare Central server to monitor have
no DNS service available, select to use the
server's IP address. Otherwise, those appliances
will be unable to post data to the server, and
status will only be available in response to
polling.
Rack Access Settings
Use this option, accessed from the NetBotz Appliance Configuration option, to configure
access to rack doors monitored by NetBotz Appliances that monitor Rack Access Pod 170
devices.
To configure Rack Access Settings, you must be a StruxureWare Central Administrator,
or a Device Administrator for the selected device group or the device group that contains
the selected NetBotz Appliance.
When no Rack Access Pod 170 devices are monitored by the selected NetBotz Appliance,
the "Rack Access Settings" display is not available.
StruxureWare Central 6.3.0
237