User Manual

Remove one or more thresholds from a notification policy for the selected device group
or device ( Remove Thresholds from Notification Policy option).
Show the notification policy to which a threshold is assigned ( Show Notification
Policy option).
Locate a device in the navigation tree from the thresholds list ( Find Device in
Navigation Tree option).
Access the "Configure Columns" display to select the attribute columns that appear
in the list ( Configure Columns icon ( )).
Enable filters that hide various threshold types and attributes. ( Filter Thresholds icon
( )).
Modifying thresholds
All thresholds use the same basic procedure and displays to modify threshold settings.
Note: The same displays are used to modify the threshold settings regardless of whether
you select:
Edit Threshold, a right-click option in the Alarm Configuration perspective.
Edit Alarm Configuration, a right-click option in the Active Alarms view in the
Monitoring perspective.
Modifying thresholds in the Alarm Configuration perspective
1.
In the Alarm Configuration perspective, select a device group, device, or threshold,
right-click to select Edit Thresholds, and select the threshold type you want to modify
from those defined for the selection.
Note: If you selected Other Numeric Sensors or Other State Sensors to modify
multiple thresholds simultaneously, the unit of measure for all selected thresholds
must be the same.
2.
In the "Edit Thresholds" display, define the threshold settings, and click OK.
Modifying thresholds in the Active Alarms view
1.
In the Active Alarms view in the Monitoring perspective, select an alarm, and right-
click to select Edit Alarm Configuration.
2.
Select This Instance to modify the threshold on the device reporting the selected
alarm only, or select All Instances to simultaneously modify the threshold on every
device on which it is defined, regardless of whether those devices are currently
reporting an alarm.
3.
Click OK.
Delete Thresholds option
This option allows you to delete thresholds for any sensor on any device.
You select a device group or device in the Navigation view of the Alarm
Configuration perspective to view the thresholds for that selection in the Threshold
Alarms Configuration view. You can then select any thresholds, with the exception of
communication link status thresholds, and delete them from the thresholds list. The
thresholds will also be deleted from any notification policy to which they were added.
StruxureWare Central 6.3.0
148