User Manual
UPS Battery Sensors:
• Battery Age
• Battery Runtime
Remaining
• Battery Capacity
Remaining
• Time Running on
Battery
Other UPS Sensors:
• UPS Age
• Input Frequency
• Output Frequency
• Output Load
• Output Power
Percent VA
Other Sensors:
• Max Number of
Output Relays
• Max Number of Input
Contacts
• Runhours of Fan
• Air Flowrate of Fan (in
cfm)
• Total Air Flow (in cfm)
• RPM Speed of Fan
State alarm thresholds
State thresholds are thresholds defined for sensors that report state values.
There are three specific types of state thresholds that can be set for state sensors.
State threshold options:
Threshold Value Description
Door Open or Closed
Settings for sensors that
determine whether a door is
open or closed.
Dry Contact Unknown, No Fault, or Fault
Settings for sensors that
determine the fault status of dry
contacts.
Motion Sensor No Motion or Motion Detected
Settings for sensors that detect
motion.
Other State Sensors Varied
Settings for sensors that
measure state settings not
reported for other Thresholds
options.
State threshold types:
Setting Description
State Threshold
An alarm occurs when the sensor state matches
the Alarm State setting.
State Mismatch Threshold
An alarm occurs when the sensor state does not
match the Normal State setting.
Note: This threshold setting is useful for sensors
that can report more than two states.
State for Time Threshold
An alarm occurs when the sensor state matches
the Alarm State setting for longer than the delay
in the Time Allowed in Alarm State setting.
State Mismatch for Time Threshold
An alarm occurs when the sensor state does not
match the Normal State setting for longer than
the time defined by the Time Allowed in Alarm
State setting.
StruxureWare Central 6.3.0
139










