Menu Items
Outlets
Control actions
You can perform Outlet Control Actions on individual outlets (by Individual
Outlet Control) or on all accessible outlets as a group (by Master Outlet
Control). You can apply a Control Action only to an outlet that is not
executing a command. If a command is pending, the State is displayed as
orange.
.
Immediate On Turns outlet on.
Immediate Off Turns outlet off.
Immediate Reboot
Turns off the outlet immediately, waits the outlets Reboot Duration
time, and turns the outlet back on. See
Immediate Reboot.
Delayed On Turns on the outlet after its Power On Delay. See
Delayed On.
Delayed Off Turns off the outlet after its Power Off Delay. See
Delayed Off.
Sequenced Reboot
(only with Master
Outlet Control)
Immediately powers off all outlets. Each outlet waits the longest
Reboot Duration time in seconds of any outlet in the set, plus its own
Power On Delay and then turns on.
Delayed Reboot
Turns off an outlet after the outlet’s Power Off Delay. After the outlet’s
Reboot Duration, the outlet is turned on. See
Delayed Off.
Delayed
Sequenced Reboot
(only with Master
Outlet Control)
Turns off each outlet after its Power Off Delay. When the outlets are
turned off, each outlet waits the longest Reboot Duration time of any
outlet in the set of outlets, plus its own Power On Delay, before the
outlet turns on.
Cancel
Cancel all pending commands to the outlets. Outlet state is displayed
in orange with an asterisk (*) when a command is pending for an
outlet.