Overload Outlet Restrictions
Outlet Restrictions prevents users from turning on outlets when the current
sensor detects an overload condition. The following restrictions can be set
for each unit:
None: Outlets always turn on.
On Warning: Outlets do not turn on when the Overload Warning
Threshold has been exceeded.
On Overload: Outlets do not turn on when the full load percentage
exceeds
100%.
Overload Audible Alarm
You can customize the Overload Audible Alarm so that it never sounds, it
sounds when the load exceeds 100%, or it sounds when the load exceeds
its Overload Warning Threshold. The value for the Overload Warning
Threshold can be set at a value that you determine based on the needs of
your system. If the Overload Audible Alarm is set to On Overload Warning
and the load exceeds the Overload Warning Threshold, the Overload
Warning
LED flashes green and the alarm sounds.
Low Current Threshold
In addition to monitoring for overload conditions, the current sensor
monitors for low-current conditions. If current drops below the Low Current
Threshold that you have defined, the unit generates an
SNMP trap to alert
the host computer.
N
ote
This item is available only in the Web/SNMP interface.