Datasheet

7
Quick Configuration
continued
Configuring
TCP/IP settings,
continued
Over the Network by ARP. To configure the
TCP/IP
settings
of the MasterSwitch
PDU
using Address Resolution Protocol
(
ARP
), perform the following steps:
1. Set up the unit and connect it to the network.
2. From a command prompt on a computer connected to
the local subnet, type arp -s ip_addr_card
mac_card. For example:
arp -s 159.215.240.22 00-c0-b7-78-ad-90
Note: To obtain the
MAC
address, see the Quality
Assurance slip, look on the bottom of the unit, or
select the TCP/IP menu from the Control
Console.
3. Type telnet ip_addr. See the example below:
telnet 159.215.240.22
The default user name and password are both apc. Configure
the correct Subnet Mask and default gateway in the TCP/IP
section of the Network menu.
Over the Network by
BOOTP
.
BOOTP
is enabled by default.
Use a
BOOTP
server to configure MasterSwitch
TCP/IP
settings and to perform the following steps:
1. Enter the MasterSwitch
MAC
address,
IP
address,
subnet mask, default gateway and optional boot-up file
name.
Note: To obtain the
MAC
address, see the Quality
Assurance slip, look on the bottom of the unit, or
select the TCP/IP menu from the Control
Console.
Continued on next page