Brochure
12
13
Vertical, 0U 208 NAM 20A, 3Φ 5.7 kW NEMA L21-20P (36) 5-20 3.0 m AP8862
Vertical, 0U 208 NAM 20 A, 3Φ 5.7 kW NEMA L21-20P (24) 5-20 (6) L6-20 3.0 m AP8863
Vertical, 0U 208 NAM 20 A, 3Φ 5.7 kW NEMA L21-20P (36) C13 (6) C19 1.8 m AP8861
(2) 5-20
Vertical, 0U 208 Japan 20 A, 3Φ 6.0 kW NEMA L21-20P (42) 5-15 1.0 m AP7862J
Vertical, 0U 208 NAM 30 A, 3Φ 8.6 kW NEMA L21-30P (36) C13 (6) C19 1.8 m AP8865
(2) 5-20
Vertical, 0U 200 – 240 NAM 50 A, 3Φ 10.0 kW CS8365C (36) C13 (6) C19 1.8 m AP8868
Vertical, 0U 200 – 240 NAM 50 A, 3Φ 14.4 kW CS8365C (24) C13 (4) C19 1.0 m AP7869
(2) L6-30
Vertical, 0U 200 – 240 NAM 50 A, 3Φ 14.4 kW CS8365C (24) C13 (4) C19 3.0 m AP7899
(2) L6-30
Vertical, 0U 200 – 240 NAM 50 A, 3Φ 14.4 kW CS8365C (6) C19 1.8 m AP7867A
Vertical, 0U 200 – 240 NAM 60 A, 3Φ 17.3 kW IEC-309 60 A 3P+PE (12) C19 (6) C13 1.8 m AP8866
Vertical, 0U 200 – 240 NAM 60 A, 3Φ 17.3 kW IEC-309 60 A 3P+PE (30) C13 1.8 m AP8867
Vertical, 0U 400 – 415 Worldwide 16 A, 3Φ 11 kW IEC-309 16 A 3P+N+PE (36) C13 (6) C19 1.8 m AP8881
Vertical, 0U 415 NAM 30 A, 3Φ 17.3 kW IEC-309 30 A 3P+N+PE (12) C19 (30) C13 1.8 m AP8887
Vertical, 0U 400 LAM, EMEA, 32 A, 3Φ 22 kW IEC-309 32 A 3P+N+PE (12) C19 (30) C13 1.8 m AP8886
GCN, APJ
Vertical, 0U 400 LAM, EMEA, 32 A, 3Φ 22 kW IEC-309 32 A 3P+N+PE (6) C19 1.8 m AP7855A
GCN, APJ
Vertical, 0U 415 NAM 40 A, 3Φ 23 kW IEC-309 60 A 3P+N+PE (12) C19 (30) C13 1.8 m AP8888
Metered Rack PDUs (continued ...)
208 V Three-phase Input
Mounting
U-space
Nominal
Power
Nominal
Voltage
Input Plug
Type
Voltage Region Input
Circuit
Output
Receptacles
Cord
Length
APC SKU
400 – 415 V
Three-phase Input
What is metered on AP8800, AP8400,
AP8900, and AP8600 Series Rack PDUs?
> Device: Power and energy
> Phase: Current*, power, and voltage
> Internal circuit breaker (bank): Current*
> Outlet: Current, power, energy
(AP8600 & AP8400 Series only)
Why do we meter?
> Device: Rack level capacity change, planning,
and efficiency calculations
> Phase: Balance loads between phases to protect
against tripping upstream branch circuit breakers
> Internal circuit breaker (bank): Protect against
tripping internal circuit breakers
> Outlet: Detailed capacity change, equipment
efficiency, and trends
*AP7000 series monitors current per phase and breaker only.