SCP. To use Secure CoPy (SCP) to upgrade firmware for the Rack PDU, follow these steps (this procedure 
assumes bootmon does not need upgrading, it is always necessary to upgrade the other two though):
1. Locate the firmware modules, see “Using the Utility for manual upgrades, primarily on Linux.” .
2. Use an SCP command line to transfer the AOS firmware module to the 
Rack PDU. The following 
example uses nnn to represent the version number of the AOS module:
scp apc_hw05_aos_nnn.bin apc@158.205.6.185:apc_hw05_aos_nnn.bin
3. Use a similar SCP command line, with the name of the application module, to transfer the application 
firmware module to the 
Rack PDU. (Always upgrade the AOS before the application module).
Use XMODEM to upgrade one Rack PDU
To use XMODEM to upgrade one Rack PDU that is not on the network, you must extract the firmware files 
from the Firmware Upgrade Utility (see “To extract the firmware files:” ).
To transfer the files (this procedure assumes bootmon does not need upgrading, it is always necessary to 
upgrade the other two though):
1. Select a serial port at the local computer and disable any service that uses the port.
2. Connect the provided serial configuration cable (part number 940-0144) to the selected port and to the 
RJ-12 style serial port at the 
Rack PDU.
3. Run a terminal program such as HyperTerminal, and configure the selected port for 57600 bps, 8 data 
bits, no parity, 1 stop bit, and no flow control.
4. Press the Reset button on the 
Rack PDU, then immediately press the Enter key twice, or until the Boot 
Monitor prompt displays: 
BM>
5. Type XMODEM, then press ENTER.
6. From the terminal program’s menu,
 select XMODEM, then select the binary AOS firmware file to 
transfer using XMODEM. After the XMODEM transfer is complete, the Boot Monitor prompt returns.
(Always upgrade the AOS before the application module).
7. To install the application module, repeat step 5 and step 6. In step 6, use the application module file 
name.
8. Type 
reset or press the Reset button to restart the Rack PDU.