Specification Sheet
Metered Rack PDUs (continued ...) 
apc.com 
|
 1312 
|
 apc.com
Vertical, 0U  208  NAM  20A, 3Φ  5.7 kW  NEMA L21-20P  (36) 5-20  3.0 m  AP8862
Vertical, 0U  208  NAM  20 A, 3Φ  5.7 kW  NEMA L21-20P  (24) 5-20 (6) L6-20  3.0 m  AP8863
Vertical, 0U  208  NAM  20 A, 3Φ  5.7 kW  NEMA L21-20P  (36) C13 (6) C19  1.8 m  AP8861 
            (2) 5-20
Vertical, 0U  208  NAM  30 A, 3Φ  8.6 kW  NEMA L21-30P  (36) C13 (6) C19  1.8 m  AP8865 
            (2) 5-20
Vertical, 0U  200 – 240  NAM  50 A, 3Φ  10.0 kW  CS8365C  (36) C13 (6) C19  1.8 m  AP8868
Vertical, 0U  200 – 240  NAM  50 A, 3Φ  14.4 kW  CS8365C  (24) C13 (4) C19  1.0 m  AP7869 
            (2) L6-30
Vertical, 0U  200 – 240  NAM  50 A, 3Φ  14.4 kW  CS8365C  (24) C13 (4) C19  3.0 m  AP7899 
            (2) L6-30
Vertical, 0U  200 – 240  NAM  60 A, 3Φ  17.3 kW  IEC-309 60 A 3P+PE  (12) C19   (6) C13  1.8 m  AP8866
Vertical, 0U  200 – 240  NAM  60 A, 3Φ  17.3 kW  IEC-309 60 A 3P+PE  (30) C13  1.8 m  AP8867
Vertical, 0U  400 – 415  Worldwide  16 A, 3Φ  11 kW  IEC-309 16 A 3P+N+PE  (36) C13 (6) C19  1.8 m  AP8881
Vertical, 0U  415  NAM  30 A, 3Φ  17.3 kW  IEC-309 30 A 3P+N+PE  (12) C19   (30) C13  1.8 m  AP8887
Vertical, 0U  400  LAM, EMEA,  32 A, 3Φ  22 kW  IEC-309 32 A 3P+N+PE  (12) C19   (30) C13  1.8 m  AP8886
    GCN, APJ
Vertical, 0U  415  NAM  40 A, 3Φ  23 kW  IEC-309 60 A 3P+N+PE  (12) C19   (30) C13  1.8 m  AP8888
208 V three-phase input
Mounting 
U-space
Nominal 
power
Nominal 
voltage
Input plug 
type
Voltage
Region Input 
circuit
Output 
receptacles
Cord 
length
APC 
SKU
400 – 415 V  
three-phase input
What is metered on AP8800, AP8400, AP8900, and 
AP8600 Series Rack PDUs? 
•Device: Power and energy
•Phase: Current,* power, and voltage
•Internal circuit breaker (bank): Current*
•Outlet: Current, power, energy 
(AP8600 & AP8400 Series only)
*AP7000 series monitors current per phase and breaker only.
Why do we meter?
•Device: Rack level capacity change, planning, 
and efficiency calculations
•Phase:Balance loads between phases to protect against 
tripping upstream branch circuit breakers 
•Internal circuit breaker (bank): Protect against tripping 
internal circuit breakers
•Outlet: Detailed capacity change, equipment efficiency, 
and trends