User Manual

5Rack ATS AP44xx Installation and Quick Start
Load Status LED
This LED identifies overload and warning conditions for the ATS. To configure warning thresholds, see
the User Guide on www.apc.com.
Network Status LED
This LED indicates the network status.
10/100 Status LED
This LED indicates the network status of the Rack ATS.
Condition Description
Green The Rack ATS current is below the Near Overload Warning
threshold.
Yellow The Rack ATS current is above the Near Overload Warning
threshold.
Red The Rack ATS current is above the Overload Alarm threshold.
Condition Description
Off The device that connects the Rack ATS to the network is off or not
operating correctly.
Flashing Green The Rack ATS is receiving data packets from the network at 10
Megabits per second (Mbps).
Flashing Orange The Rack ATS is receiving data packets from the network at 100
Megabits per second (Mbps).
Solid Green or Orange The Rack ATS is receiving no network traffic.
Condition Description
Off The Rack ATS is connected to an unknown network.
Solid green The Rack ATS has valid TCP/IP settings.
Flashing green The Rack ATS does not have valid TCP/IP settings.
1
Solid orange A hardware failure has been detected in the Rack ATS.
Flashing orange The Rack ATS is making BOOTP requests.
Flashing orange and
green (alternating)
The Rack ATS is making DHCP requests.
1
If you do not use a BOOTP or DHCP server, see “Local access to the command line interface
(CLI)” on page 11, “Remote access to the CLI” on page 11, or the User Guide on
www.apc.com to configure the TCP/IP settings.