Installation manual
Mechanical Bypass
AIS® 3000 & XR Battery Enclosure 10-40kVA, 400V, Operation Manual – 990-2259 35
Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch.
Reinstall the Front Panel
The load will now be supported directly by mains power.
Turn into normal operation (from bypass operation)
Verify the presence of mains supply
Turn the Mechanical Bypass Lever downwards (yellow BYPASS LED will switch off)
The green LOAD ON LED is now on, and the UPS is back in normal operation.
10/100Base-T
Probe
AP9619 Network Management Card EM
!
Reset
Output
Pwr
Zone
10/100
CAUTION!
Never attempt to switch back the UPS into normal operation till you have verified that
there are no internal UPS faults. Call APC Customer Support (see rear cover of this
manual) before switching back to normal operation.