Installation manual
AIS® 3000 & XR Battery Enclosure 10-40kVA, 400V, Operation Manual – 990-2259 23
Battery Replacement
General safety prior to module replacement
Battery Module
One Battery Module consists of 4 Battery Units (shipping in the Enclosures).
WARNING!
• Only trained personnel familiar with the operation of the equipment, and the
electrical and mechanical hazards involved, may install and remove system
components.
• The UPS and Battery Enclosure contain an internal energy source. Hazardous
voltage may be present even when disconnected from the power source. Follow
Total Power Off Procedure to completely de-energize the system.
• Never replace batteries when the UPS is running in battery mode!
• Risk of Energy Hazard, 96 V, 7.2 Ampere-hour battery. Before replacing
batteries, remove all conductive jewelry such as chains, watches, and rings.
High energy through conductive materials could cause severe burns.
• Batteries do not contain serviceable parts. Do not open.
• Do not open or mutilate batteries. Released material is harmful to the skin and
eyes. It may be toxic. Do not dispose of batteries in a fire, as they may explode.
• To ensure continuous battery back-up, only replace one Battery Module at a
time.
• For configurations that include customer-supplied external batteries, refer to
manufacturer’s battery installation and maintenance instructions.
Two people to lift a component weighing between 18 - 32 kg.
Note
Always exchange the whole module (all 4 units) when batteries are obsolete.
Model:
Serial:
BATTERY UNIT
Model:
Serial:
BATTERY UNIT
Model:
Serial:
BATTERY UNIT
Model:
Serial:
BATTERY UNIT
4 x 24kg