Technical information
Remote Air Cooled Condenser12
40.5° C (105° F) Ambient Condenser Flooded Receivers
APC SKU Larkin Model
Charge needed
for Larkin
Condensers
filled 100% in
kg (lbs)
System charge -
CRAC Unit
Charge + Larkin
condenser
summer charge +
Liquid line
charge between
CRAC unit and
condenser +
optional flooded
receiver
Optional
Flooded
Charge
Receiver
Dimensions
Larkin
Condenser
Summer Charge
in kg (lbs)
Flooded
Receiver
Options in
kg (lbs)
Weight - kg (lbs)
Diameter - mm
(in)
Length - mm (in)
ACCD75028
& 322
FCB-14 19.1 (42.0) 12.5 (5.7) 17.2 (37.8) 28 (62)
219 (8 5/8)
914 (36)
ACCD75301,
302, & 303
LNH-S01-A007
12FPI
11.4 (25.0) 3.7 (8.0) 10.3 (22.5) 14 (31)
152 (6)
914 (36)
ACCD75304,
305, & 306
LNH-S02-A011
12FPI
14.6 (32.0) 4.6 (10.0) 13.1 (28.8) 18 (39)
168 (6 5/8)
965 (38)
ACCD75307,
308, & 309
LNH-S02-A017
12FPI
44.1 (97.0) 13.2 (29.0) 39.7 (87.3) 48 (106)
219 (8 5/8)
1524 (60)
ACCD75316,
317, & 318
LNH-S02-A026
12FPI *
21.9 (48.0) 6.9 (15.0) 19.7 (43.2) 28 (62)
219 (8 5/8)
914 (36)
* Dual Circuit = values shown are per circuit
NOTE: Two flooded receivers are needed for dual circuited condensers (one per circuit)