Specifications
14
Control/Safety Adjustments
OVERLOAD RELAY
The blower motor starter has an adjustable
overload relay. The adjustment dial should be
set to correspond to the full load amperes (FLA)
on the blower motor. The overload has a
manual reset button to prevent the motor from
cycling on the overload switch.
FIRESTAT
The firestat used in this unit has a manual reset
and an adjustable temperature setting. The
firestat is factory set prior to shipment to trip
when temperatures above 125?F are detected.
FLOW SWITCH
If the unit is equipped with a flow switch, the
sensitivity of the switch must be adjusted for the
flow amount. Failure to do so will cause false
alarms to occur.