Specifications
Guide Specifications
30 APC NetworkAIR™ AFX
G. EVAPORATOR COIL/DRAIN PAN
1. The evaporator coil shall use the latest heat-transfer technology, raised lanced-aluminum
fins and rifle-bored copper tubes. Coil end-supports shall be galvanized steel. To enhance
dehumidification, the coil shall be split into two circuits by a microprocessor-controlled
solenoid valve. An insulated stainless steel drain pan for condensate shall be included.
H. AIR FILTER
1. The air filters shall be 30% efficient per ASHRAE Standard 52.1-92, UL Class 2. The full
4” (102 mm) deep, pleated filters shall be replaceable from the front on upflow units and
from the top on downflow units.
I. HUMIDIFIER
1. Humidifier shall be self-contained steam-generating type, factory piped and wired, with
disposable cylinder and automatic solid-state control circuit. Capacity: ______ lb/h (g/s).
J. ELECTRIC REHEAT
1. Reheat elements shall be low watt density, wired for three-phase, loaded equally on all
three phases and shall be electrically and thermally protected by both automatic and
manual reset thermal cutouts. Reheat capacity shall be ___________ MBH, ___________
kW, controlled in ________ (#) steps.
K. CONDENSATE PUMP
1. The Condensate Pump shall be factory installed and wired and shall pump 36 gal/h (0.06
L/s) at 15 ft. (4.6m) head.
L. REDUNDANT GROUP CONTROL
1. Up to six units shall have the ability to communicate with each other to automatically
switch upon alarm condition, or time rotation.
M. ENVIRONMENTAL MONITORING UNIT
1. A stand-alone unit shall perform continuous temperature and humidity sensing through
two available proves and contact monitoring. Unit shall be controlled by available web,
control console, or SNMP interface with network connection. In the event of an
environmental anomaly, notification shall be sent to the customer via e-mail or SNMP.
The unit shall be 18.25”x 9”x 2.75”(464mm x 229mm x 70mm).