Technical data

InRow RP Technical Data Manual40
PART 2 — PRODUCT
2.01 STANDARD COMPONENTS
A. CABINET CONSTRUCTION
1. Exterior panels shall be 1.2 mm (18 gauge) steel. Front and rear exterior panels shall be 1.2
mm (18 gauge) perforated steel with 69.5% open free area, and equipped with a keyed lock to
provide a means of securing access to the internal components of the unit.
2. The frame shall be constructed of 1.5 mm (16 gauge) formed steel welded for maximum
strength. All units shall provide maintenance from the front and rear, allowing units to be
placed within a row of racks.
3. All exterior panels and frame shall be powder coated for durability and attractive finish.
Exterior frame and panel color shall have color values: L = 74.50, a = -.53, b = +8.20.
4. Units shall include casters and leveling feet to allow ease of installation in the row and provide
a means to level the equipment with adjacent IT racks.
B. VARIABLE SPEED FAN ASSEMBLY
1. Variable Speed Fans: The unit is equipped with variable speed, electronically commutated,
400-mm backward incline fans complete with Inlet Volute.
2. Fan Protection: discharge finger guard. Outlet of the fan should include a cage type finger
guard.
C. AUTOMATIC TRANSFER SWITCH (CHILLED WATER ONLY)
The unit shall be equipped with an automatic transfer switch (ATS). The ATS shall automatically
switch from a main power supply to a secondary power supply in the event of a power outage
without change in equipment operation. The ATS shall monitor the main power supply so that
when the power is restored to the primary source it will automatically switch from the secondary
source back to the main power source.