Technical data

InRow RP Technical Data Manual36
Air-Cooled Condensers
Mechanical Data
SKU
Ambient
Temp
Sound
Pressure
(dbA) at 10
ft and
100% Fan
Speed
Sounds
Pressure
(dbA) at 10 ft
set area level,
and Max
Compressor
Speed
Selected
Ambient
Temp
Air Quantity Fan Unit Connection Size Weight Capacity
l/s (CFM) Qty. kW Hot Gas Liquid Kg (Lbs) MBH/1F TD kW/1C TD
ACCD75201
95 (35) 67 62 4955 (10500) 1 2.2 1 3/8 in 1 3/8 in 163 (360) 8.8 4.6
ACCD75202
105 (40) 70 65 10383 (22000) 2 4.4 1 5/8 in 1 5/8 in 290 (640) 14.6 7.7
ACCD75203
115 (46) 72 68 14819 (31400) 3 6.6 2 1/8 in 2 1/8 in
458
(1010)
25.8 13.6
ACCD75204
95 (35) 67 62 4955 (10500) 1 2.2 1 3/8 in 1 3/8 in 163 (360) 8.8 4.6
ACCD75205
105 (40) 70 65 10383 (22000) 2 4.4 1 5/8 in 1 5/8 in 290 (640) 14.6 7.7
ACCD75206
115 (46) 72 68 14819 (31400) 3 6.6 2 1/8 in 2 1/8 in
458
(1010)
25.8 13.6
ACCD75207
95 (35) 54 51 5711 (12100) 1 2.2 42 mm 22 mm 173 (381) 17.6 9.3
ACCD75208
105 (40) 57 54 11940 (25300) 2 2.2 42 mm 28 mm 307 (677) 27.1 14.3
ACCD75209
115 (46) 57 55 11374 (24100) 2 4.4 54 mm 35 mm 360 (792) 48.2 25.4
Specifications given for conditions at sea level.
Electrical Data
SKU Voltage FLA MCA MOP
ACCD75201
208-230
3 ph 60 Hz
7.0 15.0 25
ACCD75202
208-230
3 ph 60 Hz
14.0 20.0 35
ACCD75203
208-230
3 ph 60 Hz
21.0 22.8 40
ACCD75204
460
3 ph 60 Hz
3.5 15.0 15
ACCD75205
460
3 ph 60 Hz
7.0 15.0 15
ACCD75206
460
3 ph 60 Hz
10.5 15.0 20
ACCD75207
400
3 ph 50 Hz
3.7 N/A N/A
ACCD75208
400
3 ph 50 Hz
7.4 N/A N/A
ACCD75209
400
3 ph 50 Hz
7.4 N/A N/A
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection