Technical data
27InRow RP Technical Data Manual
Electrical Data
SKU Voltage MCA MOP LRA RLA FLA Hz
Power 
(kW)
ACRP100 200 - 240 80.1 100 160* 50.0 N/A 50/60 19
ACRP101 460 - 480 39.9 50 139* 23.2 N/A 60 21
ACRP102 380 - 415 N/A N/A 139* 23.2 32* 50 20
ACRP500 200 - 240 46.8 50 N/A N/A N/A 50/60 14
ACRP501 460 - 480 24.8 30 N/A N/A N/A 60 14
ACRP502 380 - 415 N/A N/A N/A N/A 24** 50 15
Note: Above data is based on maximum operating condition
*Local or national codes may require the installation of an external disconnect. The disconnect must be rated properly for the 
equipment.
**Local or national codes may require the installation of external disconnects. Two disconnects would be required and must be rated 
properly for the equipment.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
LRA - Locked Rotor Amps
RLA - Rated Load Amps
FLA - Full Load Amps