Technical data
InRow RP Technical Data Manual26
Sound Performance Data
Chilled Water Tested Sound Data
Fan 
Speed%
Airflow 
m
3
/s 
(SCFM)
Sound Power dB at Frequency Hz re: 10
-12
W Lp Sound 
Pressure dB 
re: 20 
microPa*
125 250 500 1000 2000 4000 8000 dBA dBA
35 1.13 (2500) 69.5 37.5 63.5 60.0 54.0 47.5 40.0 65.4 54.9
50 1.79 (3800) 84.0 79.0 75.5 69.5 67.5 58.5 53.5 76.9 66.8
70 2.55 (5400) 92.0 87.0 83.5 79.0 74.5 69.5 63.5 85.9 75.0
85 3.04 (6450) 92.0 95.0 89.0 84.5 79.0 74.5 69.0 90.6 80.7
100 3.26 (6900) 90.0 96.5 90.5 85.0 80.5 76.0 70.5 91.7 81.9
*Weighted Sound Pressure dBA in a 232.2 m
3 
(8200 ft
3
) room at 6 ft (1.8 m) distance.
Air-cooled Tested Sound Data
Fan 
Speed%
Airflow 
m
3
/s 
(SCFM)
Sound Power dB at Frequency Hz re: 10
-12
W Lp Sound 
Pressure dB 
re: 20 
microPa*
125 250 500 1000 2000 4000 8000 dBA** dBA
50 1.27 (2700) 84.5 87.5 78.0 77.5 75.0 66.5 65.5 83.4 72.8
75 1.79 (3800) 92.5 90.0 84.0 81.5 77.5 71.5 68.5 87.6 76.8
100 2.26 (4800) 90.0 98.0 91.0 85.0 81.0 76.5 72.0 92.3 82.8
*Weighted Sound Pressure dBA in a 8200 ft
3 
(232.2 m
3
) room at 6 ft (1.8 m) distance.
**Based on compressor operating at full speed.