Technical data

InRow RD Technical Data Manual52
N. Bridge Data Partition
1. An overhead cable distribution, that sits between adjacent NetShelter racks and allows for
removal of the unit without disrupting overhead cabling, is available as an accessory.
2. Data partition shall be constructed of 16 gauge cold rolled steel with a black powder coat
finish.
O. Cooling Fluids (ACRD200 Series)
Water and solutions of propylene or ethylene glycol up to 50% may be used. Solutions of
brine or other aqueous salt are NOT permitted.
P. Freeze Protection (ACRD200 Series)
Per ASHRAE Handbook Fundamentals 2001 21.5, a maximum of 30% ethylene glycol and
35% propylene glycol are needed for freeze protection. See the ASHRAE handbook for more
details.