Charging the equipment
Caution: This procedure is to be done by APC-trained personnel only.
R407C is a blend refrigerant. When charging equipment with blend refrigerants, only liquid refrigerant 
must be charged.
Caution: Charging with other than liquid R407C refrigerant may damage the system.
1. Ensure the ball valves are open.
2. Confirm the calculated system 
charge.
3. Connect the refrigerant cylinder to 
the charging or gauge port on the 
receiver outlet valve. Open the 
receiver valve approximately half 
way.
4. Charge liquid refrigerant into the 
high side of the system until the 
system pressures equalize. While the unit is NOT operational, charge liquid to the suction (low 
side) line to simply equalize pressures throughout the system DO NOT start the system until the 
pressure equalizes. Please note charging liquid to the suction port during operation may damage 
or reduce the life of the compressor.
5. Prior to starting the system, make sure all 
system valves are open and the system high 
side pressure remains above 15.9 bar (230 psi). 
This may require blocking the condenser inlet 
slightly. Remove any blocking panels after 
charging is complete.
6. Start the cooling unit. See “Start the cooling 
unit” on page 18
7. Once the system is operational, front seat the 
receiver service valve and continue charging 
liquid at the Schrader port down stream of the 
receiver shutoff valve, until the calculated 
charge is complete. When this procedure is 
complete, fully back seat the receiver shutoff 
valve. Leave charging hoses in place in the 
event additional charging is required.
na2455a
Service port
Schrader port
Liquid line
 LEAK
DETE CT OR 
CA BLE
SUCTIO N
DIS CHA RGE
SERVICE