Specifications
InRow RD Fluid Cooled Installation32
Specifications
Note: For additional capacity and performance data, consult the InRow RD Tec hnical Data
Manual available online at www.apc.com.
Input voltage ACRD200 - 208-240/1~/60 H
ACRD201 - 208-240/1~/50 H
Condensate pump 5 l/h (1.3 GPH), 4.9-m (16-ft) vertical rise,
15-m (50-ft) horizontal run
Physical dimensions
W x D x H - mm (in)
300 x 1070 x 1991
(11.80 x 42.13 x 78.39)
Net weight (InRow RD only) - kg (lb) 199.09 (438.5)
Shipping weight - kg (lb) 241 (532)
Cooling capacity at 29.4°C (85°F) -
kW (BTU/hour)
ACRD200: 10.90 (37,225) total
ACRD201: 10.98 (37,499) total
Sound pressure - dBA -
at 80% fan speed
76.6 dBA at 0.85 m
3
/s (1800 SCFM),
1.0 m in front of the unit
(ref 20 μPa)
Nominal fluid flow rate entering the unit - l/s (GPM) Water: 0.64 (10.0)
Glycol: 0.64 (10.0)
Entering fluid temperature range
for 0.64 l/s (10 GPM)
flow rate into the unit. - °C (ºF)
Water: 12.8 - 43.3 (55.0 - 110.0)
Glycol: 12.8 - 43.3 (55.0 - 110.0)
Maximum heat rejection - kW(BTU/hour) Water: 15.2 (52,000)
Glycol: 15.2 (52,000)
Maximum glycol percentage - % Water: 0
Glycol: 40
Pressure drop at 0.64 l/s (10 GPM) - kPa (psi) Water: 33.1 (4.8)
Glycol: 43.4 (6.3)