Installation manual
InRow RD Fluid Cooled Operation and Maintenance38
Mechanical
Electrical Hazard: Turn off the cooling unit, disconnect all power sources, and perform 
Lockout/Tagout procedures before performing any electrical or mechanical service. Wear 
appropriate personal protective equipment when checking hazardous voltages.
 Check the fans. All components should be moving freely with no signs of binding or damages. 
 Verify that the condensate line is flowing freely. 
 Verify the chilled water supply temperature for the cooling unit.
Chilled water supply temperature________________________
Electrical
Electrical Hazard: Turn off the cooling unit, disconnect all power sources, and perform 
Lockout/Tagout procedures before performing any electrical or mechanical service. Wear 
appropriate personal protective equipment when checking hazardous voltages.
 Inspect the electrical panel for tight connections and for overheated connections from loose contact 
terminals.
 Confirm the incoming main power matches the cooling unit nameplate. The measurement should be 
within 10% of the nameplate listing.