User`s guide
8 InfraStruXure InRow RC—Operation and Maintenance
Set Up Cooling Group Configuration
The cooling group configuration settings help the controller determine which components are 
available and how the cooling group should operate. 
Configure the cooling group
Path: Main > Configure Group 
The Configure Group menu contains settings that identify the 
number of cooling units installed in this cooling group and the 
physical arrangement of those cooling units.
Num Units. Indicate the number of cooling units in this cooling 
group. Up to 12 cooling units can be joined together to work as a 
single cooling group.
Type. Set the rack deployment strategy for the cooling units of this 
cooling group
• In-Row: Air flow is horizontal to allow in-row operation of 
the cooling. The loads share a common open cold aisle.
• RACS (Rack Air Containment System): Air flow in the 
enclosure is controlled by a ducting system fitted to the 
enclosure. This is not a sealed system.
• HACS (Hot Aisle Containment System): Air flow in the room is controlled by enclosing the hot 
air aisle. The loads share an enclosed common hot aisle but not sealed.
%Glycol. The percentage of glycol used by the cooling group to cool the environment affects how 
cooling output is reported. Only qualified service personnel should make changes to this setting.
Caution
The settings in the Cooling Group Configuration menu are defined by the field 
service representative when the cooling group is commissioned. Only qualified service 
personnel should make changes to these settings.
On/Standby
 View Alarms
Clear Alarms
View Event Log
na1638a
Clear Event Log
Configure Modbus
 Set Date & Time
 Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
 Service Intervals
View Run Hours
Configure Unit
Configure Group
 Set Group PID
View Group Status
 View Unit Status
Set Group Setpoints
Set Unit Thresholds
 Num Modules: 1
 Type: In-Row
 %Glycol: 15%
na1662a