Specifications

11InRow RC Operation and Maintenance
Set Up General Configuration
The cooling group configuration options are set during the commissioning of the cooling units in the
cooling group.
Caution: Changing the settings incorrectly can cause malfunctions to your cooling unit.
Only qualified service personnel should make changes to these settings.
Cooling unit configuration
Path: Main > Configure Unit > General
Capacity.
Set the cooling capacity of the cooling unit:
Select Automatic to enable the cooling unit to control its output under normal (default)
conditions.
• Select Maximum to run your cooling unit at full capacity. Use this setting when commissioning a
unit connected to a CDU to set up the proper coolant flow.
Note: Normal checks for cooling failures are disabled in the Maximum mode.
Start-up Delay. The delay begins when the cooling unit is started and initialized. The cooling unit
cannot begin operation until this delay has expired. Use the start-up delay to restart equipment
sequentially in your room after a scheduled downtime.
Idle on Leak. Set the cooling unit to enter idle mode if a leak is detected.
Power Source. Select A, B, or A&B to indicate the InRow RC power line plugged into the power
source.
Fluid Calibration. Select Fluid Cal: On to balance fluid flow through the equipment. When enabled,
the fluid valve is open 100% and the fans are on at a fixed speed (to keep the coil dry).