Specifications
7InRow RC Operation and Maintenance
Start the cooling unit
Path: Main Menu>On/Standby>Operate
Press the ENTER key to change the setting to On. The cooling unit will run according to the configured 
settings.
Stop the cooling unit
Path: Main Menu>On/Standby>Operate:
Press the ENTER key to change the setting to Standby. The cooling unit will enter the standby mode.
Warning: The Standby option does not remove power from the cooling unit. You must 
disconnect all power sources to remove power from the cooling unit.
Factory default settings
All the InRow RC settings are controlled through the display interface on the front of the InRow RC. The 
factory default temperature is set at 22.2°C (72°F). The default PID coefficient values for the Cool (Fan Speed) 
PID are:
Gain (P) = 0.67
Rate (I) = 0.37
Deriv (D) = 0.26