Pumped Refrigerant System Operation and Maintenance42
31 Primary Power Source
Overvoltage
Critical The input voltage is higher than the unit’s rated value. Connect the
unit to a properly rated voltage input.
16 Secondary Power Source
Failure
Warning • Make sure the power source is connected properly and is within
specifications.
32 Secondary Power Source
Overvoltage
Critical The input voltage is higher than the unit’s rated value. Connect the
unit to a properly rated voltage input.
7 Rack Temperature
Sensor Fault
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
10 Rack Temperature High
Violation
Critical • Make sure the temperature sensor is connected properly.
• Make sure the Rack Inlet High Temperature threshold is set
correctly in the Thresholds screen.
• If the problem persists, contact Technical Support.
30 RDU Communications
Fault
Critical • Confirm that the A-Link network has terminators on the first and
the last units in the chain.
• Confirm that the A-Link cables are connected properly to the A-
Link ports.
• If the problem persists, contact Technical Support.
11 Return Air High
Temperature Violation
Warning • Make sure the sensor is connected properly.
• Make sure the Return Air High Temperature threshold is set
correctly in the Thresholds screen.
• If the problem persists, contact Technical Support.
0 Return Air Temperature
Sensor Fault
(Front - OA, Top - RA)
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
1 Return Air Temperature
Sensor Fault
(Middle)
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
2 Return Air Temperature
Sensor Fault
(Rear - OA, Bottom - RA)
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
12 Supply Air High
Temperature Violation
Warning • Make sure the sensor is connected properly.
• Make sure the Supply Air High Temperature threshold is set
correctly in the Thresholds screen.
• If the problem persists, contact Technical Support.
3 Supply Air Temperature
Sensor Fault
(Front) OA only
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
4 Supply Air Temperature
Sensor Fault
(Rear) OA only
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
33 Unit in Maintenance
Mode
Critical • Service Technician may be troubleshooting the unit. To return the
unit to normal operation, reset the unit.
35 Upper Supply
Temperature 1 Fault
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
36 Upper Supply
Temperature 2 Fault
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
37 Upper Supply
Temperature 3 Fault
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
38 Upper Supply
Temperature 4 Fault
Critical • Make sure the sensor is connected properly.
• If the problem persists, contact Technical Support.
Alarm
Number Alarm Message Severity Action Required