Installation manual

Table Of Contents
35Pumped Refrigerant System Operation and Maintenance
Path: Main > Cooling Modules > Select CM > Status > Overview
Temperature. The temperature at each of the sensors in the selected CM.
Rack Inlet: The temperature of the air entering the rack at the remote temperature sensor.
Supply Air: The average temperature of the air entering the CM as measured by the supply air
temperature sensors.
Return Air: The average temperature of the air leaving the CM as measured by the return air
temperature sensors.
Liquid In: The temperature of the pumped refrigerant entering the CM as measured by the liquid
refrigerant temperature sensor.
Vapor Out: The temperature of the pumped refrigerant leaving the CM as measured by the vapor
refrigerant temperature sensor.
Evaporator: The evaporation temperature of the refrigerant as it leaves the evaporator.
Pressures. The pressure sensor readings:
Liquid In: The pressure of the pumped refrigerant entering the CM as measured by the liquid
refrigerant pressure transducer.
Vapor Out: The pressure of the pumped refrigerant leaving the CM as measured by the vapor
refrigerant pressure transducer.
Valve Positions. The positions of the EEV and EPRV as expressed in a percentage of a full open
condition.
EEV Pos: The current position of the Electronic Expansion Valve.
EPRV Pos: The current position of the Electronic Pressure Regulator Valve.