Installation manual

31Uniflair LE Accessories Manual
Pump Models and SKUs
The following table provides the model numbers, SKU, installation details of pumps available for Uniflair cooling
units, and pump wiring information:
External wiring: External power source. The pump is shipped loose from the factory.
Factory installed: Powered internally by the unit. The pump is factory installed.
Internal wiring: Powered internally by the unit. The pump is shipped loose from the factory.
Installation
1. Unpack and inspect the pump. If damage is observed, call Schneider-Electric Technical Support. They
will assist with repair or replacement.
2. Disconnect the electrical power at the power source (fuse box, circuit breaker, etc.) before wiring the
pump or connecting the electrical cord.
Plumbing connections
1. Position the pump so the inlet is close to and below the drain line.
NOTE: The pump must be level.
Pump Model SKU Voltage Wiring
CW-TD/UCV DX HDCV
A5X-3AP-230 ACAC76129 230 External Wiring 230 V Internal Wiring Factory Installed
A5X-3AP-460 ACAC76136 460/575 External Wiring 460 V Internal Wiring Factory Installed
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on the equipment. All electrical
work must be performed by licensed electricians. Practice Lockout/Tagout procedures.
Do not wear jewelry when working with electrical equipment.
Failure to follow these instructions will result in death or serious injury.