45EcoBreeze System Operation and Maintenance
Module powered
but will not operate
System is off
Remote shutdown or input
contact is active
System is in alarm
Turn the System on.
Check input contact configuration settings.
Check for active system alarms.
Suction pressure
too low
• Dirty or blocked evaporator coil
Low refrigerant charge
Filter drier restriction
Expansion valve closed
Erroneous sensor reading
Clean evaporator coil.
Check for proper subcooling. Repair leak and
recharge the system.
Check for excessive pressure drop. Replace the
filter drier if necessary.
Check expansion valve operation.
Check pressure and temperature sensor
operation.
Problem Possible Cause Corrective Action