Installation manual

EcoBreeze System Operation and Maintenance42
Discharge Temperature Sensor
Fault
Warning Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor.
Refrig Liquid Temperature
Sensor Fault
Warning Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor.
Condenser Coil De-Ice Active Warning Monitor the situation.
Clear the ice and snow if needed.
Filter Access Door Open
Warning
Warning Close and secure the access door.
Check the door switch and wiring.
Replace the door switch if needed.
Filter Access Door Open Alarm Critical Close and secure access door.
Check door switch and wiring.
Replace door switch if needed.
High Head Pressure Critical Check the outdoor air openings (clear obstructions).
Check the refrigerant charge.
Check operation of the outdoor fan.
Check the condenser coil for obstructions.
Reset the high pressure switch.
Low Suction Pressure Warning Check the refrigerant charge.
Check IT airflow.
Ensure that air dampers are open.
Check the condition of the air filters.
Check the condition of the evaporator coil.
Low Suction Pressure Lockout Critical Check the refrigerant charge.
Check the IT airflow.
Determine the cause of the low suction pressure.
Reset the controller.
Cap Fault or Motor Overload or
Overspeed
Critical Capacitor pre-charge fault, motor overload or motor
overspeed
Check the Alarm Code at the VFD Display:
CrF = Capacitor pre-charge fault - Reset the drive. Replace
the drive if necessary.
OLF = Compressor overload fault - Check the refrigerant
charge. Replace the compressor if necessary.
SOF = Compressor over speed fault - Check the drive
configuration.
TEMPERATURE/HUMIDITY ALARMS
Return Humidity Sensor Fault Warning • Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor.
Supply Humidity Sensor Fault Warning Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor.
Return Temperature Sensor
Fault
Warning Check the wiring.
Check and clean the sensor.
Check the sensor calibration.
Replace the sensor.