Installation manual

EcoBreeze System Operation and Maintenance36
Respond to Alarms
When an alarm is triggered, the display alerts you through the following methods:
The screen will flash Active Alarm(s) on the bottom of the main screen.
Alarm and event logs
View alarms
Path: Main > View Alarms
To view the next alarm, navigate to Next..., then press ENTER. Another method of navigating the
alarm list is to press the word First at the bottom of the screen to go to the first entry or Next...
to go to the next entry in the alarm list.
Clear alarms
Path: Main > Clear Alarms
Clear Alarms: Yes/No - Select Yes to clear all of the alarms in the list.
Reset Pump A Fault: Yes/No - Select Yes to reset a fault on water pump A.
Reset Pump B Fault: Yes/No - Select Yes to reset a fault on water pump B.
Reset Air Pump Fault: Yes/No - Select Yes to reset a fault on the air pumps.
If the conditions that caused the alarm still exist, those conditions will cause the alarm to be
regenerated. A device password must be entered to erase the alarm list.
Frame alarms
“AIRFLOW ALARMS” on page 36
“COMMUNICATION ALARMS” on page 37
“WATER SYSTEM ALARMS” on page 37
“TEMPERATURE/HUMIDITY ALARMS” on page 38
“MISCELLANEOUS ALARMS” on page 39
Name Severity Alarm Actions
AIRFLOW ALARMS
Active Flow Controller (AFC)
Sensor Fault
Critical Replace the AFC.
For assistance, contact Schneider Electric Customer
Support.
AFC Door Open Warning Close the aisle containment system door.
Check for proper operation of aisle containment door
switches.
For assistance, contact Schneider Electric Customer
Support.
AFC CAN Communication Error Critical • Check CAN cables between AFC sensors.
Power or Sensor failure of AFCs.
For assistance, contact Schneider Electric Customer
Support.