31EcoBreeze System Operation and Maintenance
DX components
• Discharge Pres.: psi/kPa - The pressure at the discharge port of the compressor.
• Discharge Temp.: °F/°C - The temperature of the refrigerant at the discharge port of the
compressor.
• Suction Pressure: psi/kPa - The pressure at the suction port of the compressor.
• Suction Temp.: °F/°C - The temperature of the refrigerant at the suction port of the
compressor.
• Compressor Power: kW - The rate of energy consumed by the compressor.
• VFD Frequency: Hz - The motor frequency command to the compressor.
• Compressor Speed: rpm - The rotational speed of the compressor.
• Superheat: °F/°C - The temperature above saturation of the refrigerant entering the
suction port of the compressor.
• EEV Position: % - The position of the electronic expansion valve.
• Liquid Temp: °F/°C - The temperature of the refrigerant in the liquid line.
Select Prev... in the lower left corner of the screen to return to the Select Module (N) screen.
From the Select Module screen, select the next Module in the list to view the status of its
sensors.
Configure Modules
Path: Main > Configure Modules
Map Modules. This function tells the Frame controller whether or not a specific Module is
populated and active within the Frame. This is the only option under mapping. You must enter
your device or admin password to change the setting.
• Module # - Present - Yes/No
Yes or No will be visible inside a highlighted box. Press ENTER to cause the highlighted box to
flash. Press the
UP or DOWN keys to change the setting. Press ENTER again to save your
changes.
Operate Modules. Allows the user to designate Modules to be on or off when the system is
operating. You must enter your device or admin password to change the setting.
• Module #
– Press the
UP or DOWN keys to select the Module # then press ENTER.
– Operate - Off/On
Off or On will be visible inside a highlighted box. Press
ENTER to cause the highlighted box to
flash. Press the
UP or DOWN keys to change the setting. Press ENTER again to save your
changes (or select Prev... to return to the previous page and select another Module to view).