Installation manual

29EcoBreeze System Operation and Maintenance
Building management system (BMS)
The Modbus interface allows the EcoBreeze to communicate with a BMS.
The Modbus connection is available in two locations on the Modbus hub of the Frame
controller:
RJ-45 In port
3-wire on terminal block
See the EcoBreeze Frame Installation Manual for more information.
Configure Modbus. If you are using a building management system with EcoBreeze, set the
following values:
N
OTE: The EcoBreeze requires two TargetIDs. The second TargetID is automatically assigned
to one greater than the value entered. When polling the EcoBreeze, always use the TargetID
entered. Do not assign TargetID + 1 to any other device.
Target ID: Each Modbus device must have a unique target identification number. Enter a
unique number from 1 to 247.
Baud rate: Select from 1200, 2400, 4800, 9600, 19200
Parity: Select from None, Even, Odd
1MOD
1MOD
D(B)
D(A)
0 V