Installation manual
EcoBreeze System Operation and Maintenance20
Configure the Frame
The Frame distributes power from the mains to the Modules and its master controllers collect
all sensor information.
The Frame also supplies the water to and from the Modules. The water system is used to wet
the outer surface of the indirect evaporative cooling (IEC) heat exchangers. Basic features of
the Frame water system include redundant pumps and flow monitor, redundant makeup water
supply, basic drain and blow-down, conductivity monitoring and control along with chemical
free water treatment.
See the water system manual for more information.
Path: Main > View Frame Status
Measurements will be visible inside a highlighted box when the screen opens. Press ENTER to
open the Measurement screen or press the
DOWN key to move to the next menu option and
press
ENTER to select your choice.
Measurements:
• Outdoor Temperature: °F/°C - The outdoor air temperature.
• Outdoor Humidity: %R.H. - The outdoor relative humidity.
• Supply Temperature: °F/°C - The temperature of the conditioned air.
• Return Temperature: °F/°C The temperature of the air to be conditioned.
• IEC Air Temperature: °F/°C - The temperature of the indirect evaporative cooled air.
• Containment DP: Pa - The differential pressure sensed between the supply air and
return.
• IT Air Flow: CFM / L/s - The volume of air flowing into the IT space.
• Compressor Power: kW - The rate at which the EcoBreeze is consuming energy to run
compressors.
• Water Conductivity: uS/cm - The conductivity of the water in the storage basin.
• Water Level: in./cm - The level of the water in the storage basin.
This is a view only screen. No changes can be made to any settings on this page.
CAUTION
AUTHORIZED PERSONNEL ONLY
Procedures in this section must be performed by Schneider Electric authorized personnel.
Changing the settings incorrectly can cause serious malfunctions and damage to your
system. Only qualified service personnel should make changes to these settings.
Failure to follow these instructions can result in injury or equipment damage.